A: Receptacle spacing:
  • The center of the 1st receptacle will be approximately 5" from the feed end
  • All duplex, twist-lock, and IEC (C13) triplex receptacles shall be spaced on 4" centers and can be placed at any position along the strip.
  • 20A IEC (C19) devices shall be spaced on 2" centers and can be placed at any position along the strip.
  • Additional spacing / length can only be selected in 4" increments.
B: Power feed selections are as follows:
  • Junction boxes sizes: 8L x 4W x 3H / 8L x 5W x 3H / 6L x 6W x 3H / 8L x 6W x 3H
  • All junction boxes come standard with an assortment of laser knockouts on all sides
  • Rigid nipples trade sizes: 1", 1 1/4" diameter and 2, 4 or 6" long
  • Greenfield trade size (Flexible metallic conduit): 1", 1 1/4" diameter and 1 to 25' long
  • Greenfield and Tails only are supplied with a adapter transition junction box
  • Configurations with extended tails shall have the wires coiled outside of the junction box, the junction box cover and screws shall be secured separately for installation on site
C: Material:
  • Junction boxes are made of steel with powder coat paint finish
  • Extrusions and covers are made of cast aluminum
  • Extrusion lengths are from 9" up to 85" (all selectable by 4" increments)
D: Power configurations:
  • 15A/ 20A 120VAC circuits with 15A duplex and 15A IEC (C13) triplex receptacles
  • 15A/ 20A 120VAC circuits with 15A duplex and 15A IEC (C13) triplex, receptacles20A 120VAC & 250VAC circuits with any combination of 20A duplex, 20A IEC (C19) single and 20A twist-lock receptacles
  • 30A 120VAC and 250VAC circuits with 30A twist-lock receptacles only
  • Isolated receptacles and circuits are provided in 20A and 30A circuits only
  • Isolated ground and standard receptacles cannot be combined on the same strip
  • IEC receptacles are non isolated only
  • All NEMA Devices are Spec grade
  • Duplex receptacle colors - (Brown, white, gray, blue, ivory and orange for isolated)
  • IEC receptacle colors - Black only
  • Twist-lock receptacle colors - Black for standard and orange for isolated
  • 20A Duplex and Twist-Lock receptacle quantities shall range from 1 to 20 devices max, (any combination)
  • IEC (C13) 15A triplex receptacle quantities shall range from 1 to 20 devices max (for a total of 60)
  • IEC (C19) 20A single devices shall range from 1 to 40 devices max
  • Raceway fills are compliant with the latest version of the NEC (National Electric Code)
  • All units come with an equipment grounding lug
  • Circuit selection:
    • You can select either all 20A circuits for a maximum circuit selection of 12 or all 30A circuits for a maximum selection of 8
    • When selecting a combination of 20A and 30A circuits the configurator is set up with a predetermined ratio between the amount of 20A and 30A circuits that can be added into the power strip, as your circuit selections are made the configurator will automatically calculate how many circuits are available for the remaining selections
    • Surge Protection
      Circuits can be selected with or without surge protection.
      Surge specifications:
      -Nominal line voltage: 120VAC
      -Maximum line current: 15A
      -Maximum allowable voltage: 125VAC (RMS)
      -Maximum clamping voltage: 395 Volts@100 amps
      -EMI/RF Suppression: More than 20db, calculated line to neutral, 100 KHz to 1 MHz suppression base upon based upon nominal impedance.
      -Peak Impulse current (8/20 micro seconds):
      30,000 amps, one time, 21,000 amps, two times within 5 minutes, 9,000 amps, ten times within 2 minutes
      Maximum multiple impulse current derated per spec.
      -Surge protection is used on 120V AC circuits only
    • Wire termination length is selectable from 12" to 48" (in six inch increments) as well as 60",72",& 84"
    • Circuit ground type:
      • Isolated with separate grounding conductors
      • Isolated with one common grounding conductor
      • Non isolated with separate grounding conductors
      • Non isolated with one common grounding conductor
  • Power fed from top or bottom of strip
  • Receptacle ground orientation is selectable (towards the top or the bottom of the strip)
  • Circuit labeling comes standard with the PDW and can be up to 15 characters long including letters and numbers
E: Safety Agency listings:
  • ETL in the USA and Canada
    USA-UL5 Canada-CSA C22.2No.62
F: Shipping:
  • Normal ship time (within 96 hours)
    • Order quantity is 10 units or less
    • Laser Engraving shall be standard receptacle circuit identification that is provided in the configurator
  • Extended shipping time (over 96 hours):
    • Order quantity is over ten units
    • Power termination is flexible conduit
    • Splicing tails longer than 12"
    • Custom laser message- Artwork is an additional $2.50, engraving is no charge
    • Custom laser logo- Artwork is an additional $30.00, engraving is no charge
    • Custom receptacle laser engraving, above and beyond what the configurator provides. Extended descriptions, special layouts and brackets for outlet groupings.
    • Any customer custom request
    • Customer Service will calculate necessary lead times based upon modified configurations
G: Additional features can be added at the customer’s request
  • PDW circuit labeling, above what the configurator has available
  • PDW comes standard up to twelve 20A circuits, if additional circuits are required the PDW can accommodate up to twenty 20A circuits with higher profile design. Configurations are custom engineered for each application
  • Custom color receptacles
  • Single outlet configurations, NEMA 5-15r & 5-20R
  • Integrated UPS circuit wiring with a separate power connection
  • Additional Greenfield trade sizes available up to 2"